ROOM REQUIREMENTS
The Room Requirements Description presents the room dimensions
requirements, weights, wall- and ceiling loads, power outlet requirements as
well as the heating, ventilation and air-conditioning (HVAC) requirements for the
TANDBERG Telepresence T3 system.
Independent of whether customers plan to install a TANDBERG Immersive
Room, or create their own, this document is important to read.
Note that the entrance door is not a part of the TANDBERG Immersive Room
package. The door should open outwards.
ROOM dIMENSIONS
Overall system dimensions:
2800mm×4800mm / 9’21⁄4”×15’9” (d×w)
Optimal room dimensions (immersive room):
4680mm×7170mm /15’41⁄4”×23’61⁄4” (d×w)
Room Height: 2550mm / 8’43⁄8
”
Note that the
door is not a part
of the Immersive
Room Package and
that the door should open
outwards.
WEIGHT ANd lOAd REQUIREMENTS
Weight of total system:
1.075kg
Weight of Wooden Wall panels:
Weight of Glass Wall Panels:
15kg/m2 (0.021lbs/inch2)
60kg (132lbs)
The Floor load for the glass panels: 240kg (528lbs) / 8 adjustable legs
This document is confidential and remains proprietary
to TANDBERG Telecom AS (“TANDBERG”).
(A=314mm2) 0.76kg/mm2 (135lbs/inch2)
Without TANDBERG’s prior written approval, this
document, either in whole or in part, may not be
reproduced in any form or by any means, disclosed
to others outside the Client’s organisation or used for
any purpose whatsoever other than for evaluatory
purposes by the Client.
Wall load for sidewalls: (for maximum size room)
Wall load for front/back wall (3.9m2):15×3.9=58.5kg (129lbs)
Wall Load for side wall (11.47m2): 15×11.47=172kg (378lbs)
All information, descriptions, examples and
calculations contained in this document are for
guidance purposes only and should not be treated as
definitive.
Ceiling load:
Ceiling lights:
Document camera: 12kg (26lbs)
42kg (92lbs)
Whilst all reasonable care has been taken to ensure
that the information contained in the presentation is
accurate and not misleading, TANDBERG shall not be
liable for any loss resulting from reliance placed on the
information contained in this document.
CONTENTS
Room requirements................................................................................................1
System dimensions................................................................................................2
Room depth requirements optimal and maximal depth .........................................3
Minimum room depth requirements ......................................................................4
Minimum room width requirements ......................................................................5
Optimum and maximum room height ....................................................................6
Minimum room height requirements .....................................................................7
Maximum room height...........................................................................................8
HVAC requirements................................................................................................9
Acoustics requirements........................................................................................11
Power outlet fuse requirements...........................................................................12
Electronic versions of Technical drawings............................................................13
TANDBERG WORLD HEADQUARTERS
Philip Pedersens vei 20
1366 Lysaker, Norway
Tel: +47 67 125 125
Fax: +47 67 125 234
Video: +47 67 126 126
E-mail: tandberg@tandberg.com
1212 Avenue of the Americas
24th Floor
New York, NY U.S.A. 10036
Tel: +1 212 692 6500
Fax: +1 212 692 6501
Video: +1 212 692 6535
E-mail: tandberg@tandberg.com
119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08
PAGE 1/22